Brand: Phoenix Contact
Category: Surge Protection Devices
- Model: 2906389
- Type 1+2 combined lightning current and surge arrester
- Pluggable lighting current arrester, in acc. with type 1/class I/B for 3-phase power supply networks with combined PE and N (L1, L2, L3, PE, N).
- Operating Voltage: 12V AC ... 250V AC and 125V DC (200mA DC)
- Operating Current: 10mA AC ... 1A AC and 1A AC (30V DC)
Nominal Voltage UN |
240/415 V AC (TN-S) |
240/415 V AC (TT) |
|
Nominal Frequency fN |
50 Hz (60 Hz) |
Maximum continious voltage Uc |
350 V AC |
Rated load current IL |
125 A (< 55°C) |
Residual current IPE |
≤ 0.01 mA |
Nominal discharge current In (8/20) µs (L-N) |
25 kA |
Nominal discharge current In (8/20) µs (L-PE) |
25 kA |
Nominal discharge current In (8/20) µs (N-PE) |
100 kA |
Maximum discharge current Imax (8/20) µs (L-N) |
50 kA |
Maximum discharge current Imax (8/20) µs (L-PE) |
50 kA |
Impulse discharge current (10/350) µs (L-N), charge |
12.5 As |
Impulse discharge current (10/350) µs (L-N), specific energy |
160 kJ/Ω |
Impulse discharge current (10/350) µs (L-N), peak current value Iimp |
25 kA |
Impulse discharge current (10/350) µs (L-PE), charge |
12.5 As |
Impulse discharge current (10/350) µs (L-PE), specific energy |
160 kJ/Ω |
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp |
25 kA |
Impulse discharge current (10/350) µs (N-PE), charge |
50 As |
Impulse discharge current (10/350) µs (N-PE), specific energy |
2500 kJ/Ω |
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp |
100 kA |
Total discharge current Itotal (10/350) µs |
100 kA |
Follow current quenching capacity Ifi (L-N) |
25 kA |
Follow current interrupt rating Ifi (N-PE) |
100 A |
Short-circuit current rating ISCCR |
25 kA |
Voltage protection level Up (L-N) |
≤ 1.5 kV |
Voltage protection level Up (L-PE) |
≤ 2.5 kV |
Voltage protection level Up (N-PE) |
≤ 1.5 kV |
Residual voltage Ures (L-N) |
≤ 1.5 kV (at In) |
Residual voltage Ures (L-PE) |
≤ 2.5 kV (at In) |
Residual voltage Ures (N-PE) |
≤ 1.5 kV (at In) |
TOV behavior at UT (L-N) |
415 V AC (5 s / withstand mode) |
440 V AC (120 min / withstand mode) |
|
485 V AC (10 h / withstand mode) |
|
TOV behavior at UT (N-PE) |
1200 V AC (200 ms / withstand mode) |
Response time tA |
≤ 100 ns |
Max. backup fuse with V-type through wiring |
125 A (gG) |
Max. backup fuse with branch wiring |
315 A (gG) |
Short-circuit current rating ISCCR |
50 kA |
Follow current quenching capacity Ifi (L-N) |
50 kA |