Type 2, TPN SPD VAL-MS 320/3+1/FM Phoenix SPD

Type 2, TPN SPD VAL-MS 320/3+1/FM Phoenix SPD

(Out of Stock)

  • Model: 2859181
Rs. 16,000.00 Rs. 14,125.00
  • Surge protective device combination
  • 4-channel, for installation on NS 35/7,5,
  • with remote indication contact (FM) as changeover contact
  • voltage 230 V AC
  • Type: DIN rail module, two-section, divisible
  • Operating voltage 5 V AC ... 250 V AC , 30 V DC
  • Operating current 5 mA AC ... 750 mA AC, 1 A DC

Type 2 surge arrester - VAL-MS 320/3+1/FM

Nominal Voltage UN

240/415 V AC (TN-S)

240/415 V AC (TT)

Nominal Frequency fN

50 Hz (60 Hz)

Maximum continious operating voltage Uc (L-N)

335 V AC

Maximum continious operating voltage Uc (L-PE)

335 V AC

Maximun continious operating voltage Uc (N-PE)

260 V AC

Rated load current lL

80 A

Residual current lPE

≤ 5 µA

Standby power consumption PC

≤ 450 mVA

Nominal discharge current In (8/20) µs

20 kA

Maximum discharge current Imax (8/20) µs

40 kA

Follow current interrupt rating Ifi (N-PE)

100 A

Short-circuit current rating ISCCR

25 kA

Voltage protection level Up (L-N)

≤ 1.5 kV

Voltage protection level U(L-PE)

≤ 1.9 kV

Voltage protection level Up (N-PE)

≤ 1.5 kV

Residual voltage Ures (L-N)

≤ 1.5 kV (at In)

≤ 1.3 kV (at 10 kA)

≤ 1.2 kV (at 5 kA)

≤ 1.1 kV (at 4 kA)

Residual voltage Ures (L-PE)

≤ 1.9 kV (at In)

≤ 1.5 kV (at 10 kA)

≤ 1.3 kV (at 5 kA)

≤ 1.2 kV (at 3 kA)

Residual voltage Ures (N-PE)

≤ 0.4 kV (at In)

≤ 0.25 kV (at 10 kA)

≤ 0.15 kV (at 5 kA)

≤ 0.1 kV (at 3 kA)

TOV behavior at UT (L-N)

415 V AC (5 s / withstand mode)

440 V AC (120 min / safe failure mode)

TOV behavior at UT (N-PE)

1200 V AC (200 ms / withstand mode)

Response time tA (L-N)

≤ 25 ns

Response time tA (L-PE)

≤ 100 ns

Response time tA (N-PE)

≤ 100 ns

Max. backup fuse with V-type through wiring

80 A (gG)

Max. backup fuse with branch wiring

125 A (gG)