- Type 1 / Class I / B arrester (lightning current arrester) replacement plug for path N-PE
- Can be combined with FLASHTRAB compact series of products
- Connection method: pluggable;
- Type : Male;
- Mode of protection N-PE; Maximum continuous voltage UC 350 V AC
Nominal Voltage UN |
240 V AC (TN - only N-PE) |
240 V AC (TT - only N-PE) |
|
Nominal Frequency fN |
50 Hz (60 Hz) |
Maximum continuous voltage Uc |
350 V AC |
Residual current IPE |
≤ 0.01 mA |
Nominal discharge current In (8/20) µs |
100 kA |
Impulse discharge current (10/350) µs, charge |
50 As |
Impulse discharge current (10/350) µs, specific energy |
2500 kJ/Ω |
Impulse discharge current (10/350) µs, peak value limp |
100 kA |
Follow current interrupt rating Ifi |
100 A (350 V AC) |
Voltage protection level Up |
≤ 1.5 kV |
Residual voltage Ures |
≤ 1.5 kV (at In) |
≤ 1 kV (at 10 kA) |
|
≤ 0.9 kV (at 5 kA) |
|
≤ 0.8 kV (at 3 kA) |
|
Front of wave sparkover voltage at 6 kV (1.2/50) µs |
≤ 1.5 kV |
TOV behavior at UT |
1200 V AC (200 ms / withstand mode) |
Response time tA |
≤ 100 ns |