Brand: Kyoritsu
Category: Insulation & Earth Testers (Meggers)
The Kyoritsu 3005A Digital Insulation and Continuity Tester uses a bargraph to display insulation resistance and displays the value of AC voltage along with a flashing symbol.
Bar graph to display insulation resistance
- Bar graph to display insulation resistance
- Displays the value of external AC voltage with flashing symbol
- Auto null function to automatically subtract the test lead resistance before displaying the real continuity resistance value
- Live circuit warning buzzer
- Releasing the test button automatically discharges the charges stored in the circuit under test
- 200mA measuring current on continuity testing
| Insulation Resistance | |
| Test voltage | 250/500/1000V |
| Measuring ranges | 20/200/2000MΩ |
| (Mid-scale value) | |
| Output voltage on open circuit | Rated test voltage |
| +20%, -0% | |
| Nominal current | 1mA DC min. |
| Output short circuit current | 1.5 mA DC approx. |
| Accuracy | ±1.5%rdg±5dgt (20/200MΩ) |
| ±10%rdg±3dgt (2000MΩ) | |
| Continuity Test | |
| Measuring ranges | 20/200/2000Ω |
| (Mid-scale value) | |
| Output voltage on open circuit | 7 - 12V DC |
| Measuring current | 200mA DC min. |
| Accuracy | ±1.5%rdg±5dgt (20Ω) |
| ±1.5%rdg±3dgt (200/2000Ω) | |
| AC Voltage | |
| AC voltage range | 0 - 600V AC |
| Accuracy | ±5%rdg±3dgt |
| General | |
| Safety Standard | IEC 61010-1 CAT III 300V Pollution Degree 2 |
| IEC 61010-2-031, IEC 61010-2-034, IEC 61557-1,2,4 | |
| IP Rating | IEC 60529-IP54 |
| EMC Standard | IEC 61326-1 |
| Power source | R6 (AA) (1.5V) × 8 |
| Dimension | 167(L) × 185(W) × 89(D)mm |
| Weight | Approx. 970g |